Fire Dampers Type ‘FKRS-EU’

COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES

Small circular fire damper for the isolation of duct penetrations between fire compartments, available in ten nominal sizes

  • Nominal sizes: 100 – 315 mm
  • Low differential pressure and sound power level
  • Optional stainless steel casing or powder-coated casing for increased corrosion protection
  • Can also be used as an air transfer unit
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options
Customise & Add To
Your Quote Request List

You must be logged in to view product options

Product Information

Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C
  • Duct smoke detector RM-O-3-D

  • With fusible link
  • With spring return actuator
  • With cover grilles both ends as air transfer unit with general building inspectorate licence: Z-19.18-2128

  • Dry mortarless installation into solid walls and ceiling slabs, lightweight partition walls, fire walls, and shaft walls using an installation block
  • Installation with wall face frame on the face of solid walls
  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Approved installation orientation from 0° to 360°

  • Limit switch for damper blade position indication
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Network module for the integration with AS-i or LON networks

  • Circular installation block ER
  • Square installation kit TQ
  • Wall face frame WA
  • Installation kit GL
  • Cover grille
  • Flexible connectors
  • Extension piece

 

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D

  • Rigid circular casing suitable for push fitting into cut circular holes without additional drilling and chiselling being required
  • Spigot connections with lip seal on both ends, suitable for ventilation ducts according to EN 1506 and EN 13180 plus non-standard but commercial nominal sizes 180, 224 and 280
  • Suitable for the connection of flexible connectors or cover grilles
  • The release mechanism is accessible and can be tested from the outside
  • One inspection access panel
  • Remote control with spring return actuator

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301

  • Special insulation material
  • Special insulation material with coating

  • Damper blade shaft made of galvanised steel or stainless steel
  • Plastic bearings
  • Seals of elastomer

The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request

  • Construction Products Regulation
  • EN 15650:2010 Ventilation for buildings – Fire dampers
  • EN 1366-2:1999 Fire resistance tests for service installations – Fire dampers
  • EN 13501-3:2010 Fire classification of construction products and building elements
  • EN 1751:1999 Ventilation for buildings – Air terminal devices

  • The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
  • A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
  • Fire dampers must be included in the regular cleaning schedule of the ventilation system.
  • For details on maintenance and inspection refer to the installation and operating manual