Fire Dampers Type ‘FK-EU’

FOR DIVERSE APPLICATIONS

Rectangular fire damper for the isolation of duct penetrations between fire compartments, for a variety of installation situations, available in many different sizes and constructions

  • Nominal sizes 200 × 200 – 1500 × 800 mm, in increments of 1 mm
  • Low differential pressure and sound power level
  • Explosion-proof construction (ATEX) as an option
  • Can also be used as an air transfer damper
  • Optional stainless steel casing or powder-coated casing for increased corrosion protection
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options
Customise & Add To
Your Quote Request List

You must be logged in to view product options

Product Information

Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C
  • Duct smoke detector RM-O-3-D

  • With fusible link
  • With fusible link for use in potentially explosive atmospheres
  • With spring return actuator
  • With spring return actuator for use in potentially explosive atmospheres
  • With spring return actuator and duct smoke detector
  • With spring return actuator, duct smoke detector and cover grilles on both ends for use as an air transfer opening, with general building inspectorate licence Z-6.50-2031

  • Fire dampers with casing length L = 500 mm only for installation: with installation subframe and installation kit; with installation kit for lightweight partition walls; adjacent to solid walls and remote from solid walls
  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Single-handed operation

  • Limit switch for damper blade position indication
  • Limit switch for damper blade position indication for use in potentially explosive atmospheres
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Spring return actuator for 24 – 230 V supply voltage, for use in potentially explosive atmospheres
  • Network module for the integration with AS-i or LON networks
  • Spring return actuator and pre-wired duct smoke detector, 24 V or 230 V supply voltage

  • Installation subframe and installation kit for dry mortarless installation in solid walls
  • Installation kit for installation into solid non-load-bearing walls with flexible ceiling joint
  • Installation kit for dry mortarless installation on the face of solid walls
  • Installation kit for dry mortarless installation adjacent to solid walls
  • Installation kit for dry mortarless installation remote from solid walls and ceiling slabs
  • Installation kit for dry mortarless installation in lightweight partition walls/fire walls with metal support structure and cladding on both sides
  • Installation kit for dry mortarless installation into shaft walls with or without metal support structure but with cladding on one side
  • Installation kit for installation into lightweight partition walls with flexible ceiling joint
  • Flexible connectors
  • Cover grille
  • Circular spigots

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D

  • Rectangular or square construction, rigid casing, both flanges with fixing holes
  • Suitable for the connection of ducts, spigots, flexible connectors or a cover grille
  • The release mechanism is accessible and can be tested from the outside
  • Two inspection access panels
  • Remote control with spring return actuator

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301

  • Special insulation material
  • Special insulation material with coating

  • Damper blade shafts and driving linkage made of stainless steel
  • Brass or stainless steel bearings
  • Seals of polyurethane or elastomer

 

The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request.

  • Construction Products Regulation
  • EN 15650:2010 Ventilation for buildings – Fire dampers
  • EN 1366-2:1999 Fire resistance tests for service installations – Fire dampers
  • EN 13501-3:2010 Fire classification of construction products and building elements
  • EN 1751:1999 Ventilation for buildings – Air terminal devices

  • The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
  • A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
  • Fire dampers must be included in the regular cleaning schedule of the ventilation system.
  • For details on maintenance and inspection refer to the installation and operating manual